INDOOR AIR QUALITY (IAQ) AND WHAT'S NEW IN ASHRAE 62.1-2022

ASHRAE 62.1: The primary standard for commercial/high-occupancy buildings, specifying the minimum outdoor air flow rate for each space, with the aim of ensuring air quality, health and energy efficiency.

번역 업데이트 중

English version machine-translated from the Vietnamese original — under review.

1. Introduction to ASHRAE 62.1

  • Purpose: Sets minimum outdoor air supply rates for each type of space in commercial buildings, to ensure that indoor air quality meets human health and perception requirements
  • Scope: Not intended for residential dwellings (covered by Standard 62.2), and not applicable to smoking areas or healthcare facilities (which have moved to ASHRAE 170)

2. Evolution of the Editions

  • The standard is continuously maintained and updated. The 2019 edition (and the latest, 2022) focuses on expansion: covering both the IAQ procedure and natural ventilation, and removing sections that are no longer relevant (for example: smoking areas)

3. The Three Main Design Procedures in the Standard

  1. Ventilation Rate Procedure (VRP): A method that determines the outdoor air flow rate based on the occupant density and floor area of each space. This is the most commonly used method
  2. Indoor Air Quality Procedure (IAQP): A method based on actual air performance (including filtration systems and contaminant control), allowing more flexibility than VRP if supported by data.
  3. Natural Ventilation Procedure: Design based on natural ventilation, which must take into account climatic conditions, window area and the ability to measure air circulation

4. Other Important Factors

  • Air classification (Air Class): Determines the level of outdoor pollution so that design inputs are appropriate (for example, near industrial zones or busy roads…).
  • Building envelope and HVAC system construction issues: Floor plan density, envelope tightness and the HVAC systems all affect the ability to supply/exhaust and circulate air.
  • Operation and maintenance: Ensures the system maintains its design air supply performance throughout its service life.

5. A Practical Example: Saving Energy While Still Ensuring IAQ

  • According to recent updates (for example the article "Optimizing ventilation…"):
    • Apply VRP and suitable exhaust systems for each type of space (such as bathrooms and toilets, with two flow rate levels: continuous vs intermittent).
    • Calculate the design density based on the highest number of people that may be present to ensure the system operates effectively.

Conclusion

  • ASHRAE 62.1: The primary standard for commercial/high-occupancy buildings, specifying the minimum outdoor air flow rate for each space, with the aim of ensuring air quality, health and energy efficiency.
  • The latest edition (2022) expands with a more flexible IAQ approach and removes sections that are no longer relevant, while retaining the 3 core design procedures.
  • Practical application needs to balance system design (air quality), operation (maintenance, dimming) and energy-saving goals.

6. How to Calculate VRP for Each Type of Space

VRP (Ventilation Rate Procedure) is the most common design method in ASHRAE 62.1, requiring:

Outdoor air supply flow rate = (Rp × Pz) + (Ra × Az) Where:

  • Rp = Flow rate per person (L/s.person)
  • Pz = Design number of people in the zone
  • Ra = Flow rate per unit area (L/s.m²)
  • Az = Zone floor area

Calculation example:

Space: Office

  • Rp = 5 L/s.person
  • Ra = 0.6 L/s.m²
  • Area Az = 100 m²
  • Design number of people Pz = 10

Calculation:

  • Per person: 5 × 10 = 50 L/s
  • Per area: 0.6 × 100 = 60 L/s → Total flow rate: 110 L/s

Notes:

  • The Rp and Ra values for each type of space are given in detail in Table 6-1 (ASHRAE 62.1).
  • Spaces with high occupant density (e.g. classrooms, conference rooms) have a high Rp. Spaces that are not regularly occupied (e.g. storage rooms) have almost only Ra.

7. How to Apply the IAQP (Indoor Air Quality Procedure)

IAQP is a design method based on actual contaminant concentrations instead of applying a fixed formula as in VRP.

How to carry out the IAQP:

  1. Identify the main contaminants: CO₂, VOCs, formaldehyde, PM2.5…

  2. Determine the target concentrations: Based on international guidelines (EPA, WHO or ASHRAE Appendix B).

  3. Calculate the minimum outdoor air needed to keep these contaminants at acceptable levels, which may be combined with:

    • Air filters (HEPA, carbon…)
    • In-room air treatment devices (e.g. ionization, UV-C)
    • CO₂ concentration control systems or automatic VOC sensors

Advantages:

  • Reduced outdoor air flow rate → energy savings
  • Better optimized for smart buildings, large offices or flexible spaces

Limitations:

  • Requires a specific air quality analysis
  • Requires simulation reports & field measurements

8. Notable Changes in ASHRAE 62.1-2022

Topic What's new (2022)
Removal of smoking areas Air supply for "smoking areas" is no longer calculated
IAQ zoning Clearer definition of each "air class" and the rules for air transfer
Ventilation Zone Distribution Effectiveness (Ez) Additional explanation of how to select Ez in zoned systems (zone-level supply)
Natural Ventilation Updated requirements for verifying weather conditions, with clearer aerodynamic measurement
Building Envelope Impact Requires checking and simulating the effect of air leakage (envelope leakage) on the ventilation system
Energy analysis Refers to combining with ASHRAE 90.1 (Energy Standard) when using IAQP to save energy

Conclusion

Situation Recommended method
Conventional, simple projects VRP (easy to use, standard values readily available)
Energy-saving, high-end projects with IAQ control IAQP (flexible, technically demanding)
Open spaces, natural ventilation, or special designs Natural Ventilation Procedure

9. Rp / Ra REFERENCE TABLE – ASHRAE 62.1-2022 (Table 6-1)

Space type Default occupant density (people/m²) Rp (L/s.person) Ra (L/s.m²)
Office (Office space) 0.06 5.0 0.6
Meeting room (Conference room) 0.12 3.8 0.3
Classroom (Classroom: ages 5–8) 0.25 5.0 0.9
Classroom (Classroom: > 9 years) 0.25 2.5 0.9
Auditorium (Lecture hall) 0.5 3.8 0.3
Restaurant / dining (Dining) 0.7 5.0 0.6
Fitness room (Gym) 0.4 10.8 0.8
Cinema / Theater 0.15 3.8 0.3
Hospital – patient room 0.125 2.4 0.6
Hotel – bedroom 0.06 5.0 0.3
Corridor area (Corridor) Rp not applied — 0.3
Public restroom (Public toilet) Rp not applied — 0.5
Storage room Rp not applied — 0.3
Reception / Waiting lobby (Lobby) 0.1 3.8 0.3
Laboratory (Dry lab) 0.06 5.0 1.8

Notes:

  • Rp: Required outdoor air flow rate per person (liters/second/person).
  • Ra: Required outdoor air flow rate per square meter of floor area (liters/second/m²).
  • The total outdoor air supply flow rate for each zone is calculated using the formula:
    • Pz: Design number of people
    • Az: Zone floor area (m²)

Voz = Rp × Pz + Ra × Az

Where:

  • Pz: Design number of people
  • Az: Zone floor area (m²)

Below is a summary table of indoor air quality (IAQ) indicators related to CO₂, humidity, VOCs, PM2.5 and PM10 according to ASHRAE 62.1-2022 and the reference documents used by ASHRAE.

Important note: ASHRAE 62.1-2022 does not directly specify a particular "maximum limit" for every contaminant; rather, it requires them to be controlled at levels that do not affect health or perception, and refers to other documents such as WHO, EPA, OSHA, etc. – especially where the IAQP (Indoor Air Quality Procedure) is applied.

1. CO₂ – Carbon Dioxide

Control level Recommended value Reference source
Acceptable IAQ limit ≤ 1,000 ppm (relative to outdoors) ASHRAE 62.1 Appendix C
Default outdoor concentration ≈ 400–420 ppm Design note
Alarm concentration for unacceptable IAQ ≥ 1,200 ppm Common practice, school regulations

IAQP target: keep indoor CO₂ ≤ 700 ppm above outdoors (~1,100–1,200 ppm in total)

2. Relative Humidity (RH)

IAQ condition Proposed value Notes
Optimal RH for IAQ 40% – 60% Recommended by ASHRAE
Recommended maximum limit ≤ 65% Prevents mold and bacteria
Minimum limit ≥ 30% Prevents dry nose and dry skin

ASHRAE 62.1 recommends maintaining reasonable humidity; it does not specify a hard figure, but requires humidity to be controlled to prevent mold and adverse health effects.

3. VOCs – Volatile Organic Compounds

Total VOC index (TVOC) Limit (µg/m³) Reference
Acceptable (IAQP) ≤ 500 µg/m³ WHO, LEED
Good (ideal level) ≤ 200 µg/m³ WELL v2, RESET
IAQ alarm threshold ≥ 1,000 µg/m³ May affect health

ASHRAE does not specify a particular VOC threshold, but if IAQP is used, common VOCs (formaldehyde, benzene, toluene...) must be kept at levels that do not affect health or perception.

4. PM2.5 and PM10 – Fine Particulate Matter

Particle type Recommended maximum (24h average) Source
PM2.5 ≤ 15 µg/m³ WHO 2021; referenced by ASHRAE
PM10 ≤ 45 µg/m³ WHO 2021

With IAQP, if PM sensors and filtration are installed, fine particulate matter must be kept below the WHO thresholds for IAQ to be acceptable.

Summary – Minimum IAQ Control Levels for IAQP (suggested for practical use)

Parameter Safe design threshold
CO₂ ≤ 1,000 ppm
RH 40 – 60% RH
TVOC ≤ 500 µg/m³
PM2.5 ≤ 15 µg/m³
PM10 ≤ 45 µg/m³

Conclusion

  • ASHRAE 62.1-2022 requires air quality to be controlled so that it does not affect health or perception, especially when IAQP is used.
  • Further details of the reference documents, such as WHO, EPA and OSHA, can be found in Appendices B, C and E of ASHRAE 62.1-2022.
  • The above criteria are usually combined with IAQ sensors, air filtration and smart CO₂ control systems in modern buildings.