电加热器选型表 — S-VAV-SE / S-VAV-SP
带电加热(S-VAV-SE)或 PTC(S-VAV-SP)再热的单风道 VAV 末端:各尺寸在不同供热风量下的功率、电流和出风温度(LAT)。与 S-VAV-SW / SE / SP 样本中的表格相同。
电加热 / PTC 选型
计算值 – 未经试验每尺寸三种标准配置。EAT 13 °C、供热风量 = 额定 30 / 50 / 80 % 时的 LAT。Q 最小:A × B 截面风速 0.5 m/s(风量开关设定),低于此切断加热。电流:单相 230 V / 三相 400 V。
| 尺寸 额定 Q m³/h | Q 最小 m³/h | 配置 | kW | A(单相 / 三相) | 额定 Q 的 30 / 50 / 80 % 时 LAT °C | ΔP E / P, Pa | ||
|---|---|---|---|---|---|---|---|---|
| 30 % | 50 % | 80 % | ||||||
| 4″ 255 m³/h | 93 | 1x1.5 | 1.5 | 6.5 / 2.2 | 71.5 | 48.1 | 34.9 | 1.1 / 2.8 |
| 2x1.5 | 3.0 | 13.0 / 4.3 | 130.0 | 83.2 | 56.9 | |||
| 2x3 | 6.0 | 26.1 / 8.7 | 247.0 | 153.4 | 100.8 | |||
| 5″ 425 m³/h | 93 | 1x1.5 | 1.5 | 6.5 / 2.2 | 48.1 | 34.1 | 26.2 | 3.1 / 7.9 |
| 2x1.5 | 3.0 | 13.0 / 4.3 | 83.2 | 55.1 | 39.3 | |||
| 2x3 | 6.0 | 26.1 / 8.7 | 153.4 | 97.2 | 65.7 | |||
| 6″ 680 m³/h | 93 | 1x1.5 | 1.5 | 6.5 / 2.2 | 34.9 | 26.2 | 21.2 | 8.0 / 20 |
| 2x1.5 | 3.0 | 13.0 / 4.3 | 56.9 | 39.3 | 29.5 | |||
| 2x3 | 6.0 | 26.1 / 8.7 | 100.8 | 65.7 | 45.9 | |||
| 7″ * 934 m³/h | 128 | 1x2.5 | 2.5 | 10.9 / 3.6 | 39.6 | 29.0 | 23.0 | 8.0 / 20 |
| 2x2.5 | 5.0 | 21.7 / 7.2 | 66.2 | 44.9 | 32.9 | |||
| 2x5 | 10.0 | 43.5 / 14.4 | 119.4 | 76.8 | 52.9 | |||
| 8″ 1189 m³/h | 128 | 1x2.5 | 2.5 | 10.9 / 3.6 | 33.9 | 25.5 | 20.8 | 13 / 33 |
| 2x2.5 | 5.0 | 21.7 / 7.2 | 54.8 | 38.1 | 28.7 | |||
| 2x5 | 10.0 | 43.5 / 14.4 | 96.6 | 63.1 | 44.3 | |||
| 9″ * 1529 m³/h | 195 | 1x2.5 | 2.5 | 10.9 / 3.6 | 29.3 | 22.8 | 19.1 | 9.2 / 23 |
| 2x2.5 | 5.0 | 21.7 / 7.2 | 45.5 | 32.5 | 25.2 | |||
| 2x5 | 10.0 | 43.5 / 14.4 | 78.0 | 52.0 | 37.4 | |||
| 10″ 1869 m³/h | 195 | 1x3 | 3.0 | 13.0 / 4.3 | 29.0 | 22.6 | 19.0 | 14 / 34 |
| 2x3 | 6.0 | 26.1 / 8.7 | 44.9 | 32.1 | 25.0 | |||
| 2x6 | 12.0 | 52.2 / 17.3 | 76.8 | 51.3 | 36.9 | |||
| 12″ 2718 m³/h | 277 | 1x3 | 3.0 | 13.0 / 4.3 | 24.0 | 19.6 | 17.1 | 14 / 36 |
| 2x3 | 6.0 | 26.1 / 8.7 | 34.9 | 26.2 | 21.2 | |||
| 2x6 | 12.0 | 52.2 / 17.3 | 56.9 | 39.3 | 29.5 | |||
| 14″ 3568 m³/h | 397 | 1x5 | 5.0 | 21.7 / 7.2 | 26.9 | 21.4 | 18.2 | 12 / 30 |
| 2x5 | 10.0 | 43.5 / 14.4 | 40.9 | 29.7 | 23.4 | |||
| 2x10 | 20.0 | 87.0 / 28.9 | 68.7 | 46.4 | 33.9 | |||
| 16″ * 4757 m³/h | 480 | 1x5 | 5.0 | 21.7 / 7.2 | 23.4 | 19.3 | 16.9 | 15 / 37 |
| 2x5 | 10.0 | 43.5 / 14.4 | 33.9 | 25.5 | 20.8 | |||
| 2x10 | 20.0 | 87.0 / 28.9 | 54.8 | 38.1 | 28.7 | |||
LAT > 32 °C 不可用(LAT > 50 °C 或低于 Q 最小)
* 7″、9″ 内插,16″ 外推(S-VAV-S 数据)
橙色:LAT > 32 °C(超过 ASHRAE 62.1 对吊顶送风的建议);红色:LAT > 50 °C 或风量低于 Q 最小 — 不可用,选更小配置或提高供热风量。超温保护 60 °C。电源:≤ 4.5 kW 单相,以上三相。
使用引擎 vav-rh@1 计算(S-VAV-S 箱体数据为 Intertek 实测;再热段未经试验)。额定 Q = S-VAV-S 样本中各尺寸的基准风量。
带电加热的风机动力型末端(S-VAV-PFE):进风为混合风——请在 VAV 快速选型工具中选型。