Back

Electric heater selection table — S-VAV-SE / S-VAV-SP

Single-duct VAV boxes with electric (S-VAV-SE) or PTC (S-VAV-SP) reheat: capacity, current and leaving-air temperature (LAT) by heating airflow for each size. Same table as in the S-VAV-SW / SE / SP catalogue.

Electric / PTC heater selection

Calculated – not tested

Three standard options per size. LAT at EAT 13 °C for heating airflow = 30 / 50 / 80 % of rated airflow. Q min: 0.5 m/s across the A × B section (airflow-switch setting); below it the heater is disabled. Current: 1-phase 230 V / 3-phase 400 V.

Size
Rated Q m³/h
Q min m³/hOptionkWA (1-ph / 3-ph)LAT °C at 30 / 50 / 80 % of rated QΔP E / P, Pa
30 %50 %80 %
4″
255 m³/h
93 1x1.5 1.5 6.5 / 2.2 71.548.134.9 1.1 / 2.8
2x1.5 3.0 13.0 / 4.3 130.083.256.9
2x3 6.0 26.1 / 8.7 247.0153.4100.8
5″
425 m³/h
93 1x1.5 1.5 6.5 / 2.2 48.134.126.2 3.1 / 7.9
2x1.5 3.0 13.0 / 4.3 83.255.139.3
2x3 6.0 26.1 / 8.7 153.497.265.7
6″
680 m³/h
93 1x1.5 1.5 6.5 / 2.2 34.926.221.2 8.0 / 20
2x1.5 3.0 13.0 / 4.3 56.939.329.5
2x3 6.0 26.1 / 8.7 100.865.745.9
7″ *
934 m³/h
128 1x2.5 2.5 10.9 / 3.6 39.629.023.0 8.0 / 20
2x2.5 5.0 21.7 / 7.2 66.244.932.9
2x5 10.0 43.5 / 14.4 119.476.852.9
8″
1189 m³/h
128 1x2.5 2.5 10.9 / 3.6 33.925.520.8 13 / 33
2x2.5 5.0 21.7 / 7.2 54.838.128.7
2x5 10.0 43.5 / 14.4 96.663.144.3
9″ *
1529 m³/h
195 1x2.5 2.5 10.9 / 3.6 29.322.819.1 9.2 / 23
2x2.5 5.0 21.7 / 7.2 45.532.525.2
2x5 10.0 43.5 / 14.4 78.052.037.4
10″
1869 m³/h
195 1x3 3.0 13.0 / 4.3 29.022.619.0 14 / 34
2x3 6.0 26.1 / 8.7 44.932.125.0
2x6 12.0 52.2 / 17.3 76.851.336.9
12″
2718 m³/h
277 1x3 3.0 13.0 / 4.3 24.019.617.1 14 / 36
2x3 6.0 26.1 / 8.7 34.926.221.2
2x6 12.0 52.2 / 17.3 56.939.329.5
14″
3568 m³/h
397 1x5 5.0 21.7 / 7.2 26.921.418.2 12 / 30
2x5 10.0 43.5 / 14.4 40.929.723.4
2x10 20.0 87.0 / 28.9 68.746.433.9
16″ *
4757 m³/h
480 1x5 5.0 21.7 / 7.2 23.419.316.9 15 / 37
2x5 10.0 43.5 / 14.4 33.925.520.8
2x10 20.0 87.0 / 28.9 54.838.128.7

LAT > 32 °C Not allowed (LAT > 50 °C or below Q min)

* sizes 7″, 9″ interpolated, 16″ extrapolated in the S-VAV-S data

Orange: LAT > 32 °C (above the ASHRAE 62.1 recommendation for ceiling supply); red: LAT > 50 °C or airflow below Q min — not allowed, choose a smaller option or raise the heating airflow. High-limit cut-out at 60 °C. Supply: ≤ 4.5 kW single-phase, above three-phase.

Calculated with engine vav-rh@1 (S-VAV-S box data measured by Intertek; the reheat section is not tested). Rated Q = the anchor airflow of each size in the S-VAV-S catalogue.

Fan-powered boxes with electric heat (S-VAV-PFE): the entering air is mixed air — select them in the VAV quick selector.