GRILLES · DIFFUSERS · LOUVERS

Grilles, diffusers and louvers

Extruded aluminium, powder-coated on an automated line at the Starduct factory, Hanoi. SAG, DAG, SKD and SLD are measured by Intertek (USA) to ASHRAE 70.

Slide 1 / 15
Made in the Starduct factory, tested by independent laboratoriesMade in the Starduct factory, tested by independent laboratoriesMade in the Starduct factory, tested by independent laboratories

Made in Vietnam · Supplied to 17 markets

Made in the Starduct factory, tested by independent laboratories

AMCA · AHRI · ASHRAE · VISRAEMember of international and Vietnamese HVAC engineering associations
UL · FM · Intertek · IBST · VIBMRegular testing and certification with independent laboratories
5 patentsGranted in Vietnam
In-house aerodynamic test labPressure drop, airflow and leakage measured at the factory

“Vietnamese engineering can do it — and do it better.”

Grilles, diffusers and louversSlide 2 / 15

Slide 2 / 15
Measured data, not estimates

GRILLES · DIFFUSERS · LOUVERS

Measured data, not estimates

SAG, DAG, SKD and SLD tested by Intertek (Cortland, New York) to ASHRAE 70-2006; other models and sizes are calculated from the measurements or from theory.

50grille, diffuser, louver and displacement models
4models measured by Intertek to ASHRAE 70-2006
4product groups: grilles, diffusers, louvers, displacement

Grilles, diffusers and louversSlide 3 / 15

Slide 3 / 15
Slide 4 / 15
Slide 5 / 15
Slide 6 / 15
Slide 7 / 15
Slide 8 / 15
Slide 9 / 15

MEASURED & CALCULATED

Each model states measured or calculated

4 Measured (test report)Samples measured by Intertek (USA) to ASHRAE 70-2006; other sizes calculated from the measurements. DAG · SAG · SKD · SLD
3 Cross-geometry from a tested model – not testedCross-calculated from the measurements of a tested model. SCLB · SCLB-LS · SKD-S
37 Calculated – not testedCalculated from aerodynamic theory: outlets on an ASHRAE 70 basis, louvers on an AMCA 500-L basis. SAD · SECG · SFB · SPG · SRAG · SRRAG · SWL · SAL-F · SAL-V · SSL · WWL-E · WWL-K · WWL-V · FK025 · FK026 · FK028 · FK037 · FK043 · FK048 · SKD-K1 · SKD-K2 · SKD-K3 · SRD-1 · STD · STR-1R · STRD · SWF · SDV-W1 · SDV-W3 · SDV-K · SDV-HR · SDV-R · SDV-F · SDV-SR · SDV-T · SDV-TH · SDV-D
6 Test pendingNo performance data published yet. SAC · FK041 · SRD-2 · SRD-4 · STR-2R · SWS

Intertek reports apply only to the samples tested; tables for other sizes are calculated by Starduct and not verified by Intertek.

Grilles, diffusers and louversSlide 10 / 15

Slide 10 / 15

TESTING

Intertek reports to ASHRAE 70-2006

ANSI/ASHRAE 70-2006 · ADC 1062 GRD-84Characteristics tested: octave-band sound power and NC; airflow vs static pressure; area factor Ak; throw pattern. Isothermal air. NC = Lw − 10 dB room absorption.
Intertek reports SAG 104519155CRT-001a (2021)DAG 104519155CRT-001b (2021)SKD 104519155CRT-001cSLD 104519155CRT-001d
ISO 9001 · ISO 14001ISO 9001:2015 (VN-10161-QMS) · ISO 14001:2015 (VN-10038-EMS).

Grilles, diffusers and louversSlide 11 / 15

Slide 11 / 15
Materials

MATERIALS & FINISH

Materials

01Aluminium frame and bladesFrame and blades: extruded aluminium A6063-T5, 1.0–1.2 mm
02Blades and corner keysOval blades 16.5 × 5 mm or teardrop blades, fixed with matching aluminium pins · Pressed aluminium corner keys against twist and paint cracking; stiffener for W > 600 mm
03Powder coatingHigh-grade Jotun powder coating on a 5-stage automated line; RAL 9010 matt white or any RAL code
0410-year colour durability warrantyIndoor installation, atmospheric corrosivity up to C2 per ISO 12944-2 (C1–C2).

Humid indoor, coastal or exterior: two premium Jotun systems, warranted by Jotun directly to the customer.

Grilles, diffusers and louversSlide 12 / 15

Slide 12 / 15
Frameless: only the blades remain visible

Installed: SLD Frameless in a gypsum ceiling

FRAMELESS

Frameless: only the blades remain visible

01Frame skimmed into the ceilingSLD, SAG and DAG are available with a Frameless frame: the flange is a flat, perforated 1 mm aluminium strip. After installation it is taped and skimmed into the ceiling, leaving only the blades visible.
02Same performanceSame blade core and performance data as the standard model
03Colours and curvesWhite, black or any RAL; curved versions available
04InstallationHang the plenum independently on rods; do not load the ceiling board with it.

Grilles, diffusers and louversSlide 13 / 15

Slide 13 / 15

SELECTING AN OUTLET

Selecting an outlet in five steps

01Airflow & NCSet the airflow per outlet and the room's target NC.
02Pick the sizeIn the performance table, pick the smallest size with NC ≤ target at the required airflow. Linear interpolation between columns is adequate.
03ThrowCheck throw against ASHRAE ADPI ratios for the room's characteristic length.
04Fan pressureAdd Pt to duct losses for fan sizing.
05CorrectionsCorrect where installation differs from the test: several outlets, partly closed OBD, cold supply, deflected blades.

Grilles, diffusers and louversSlide 14 / 15

Slide 14 / 15

CONTACT

Select, submit and order

Size outlets in the quick selector, download catalogues and documents from the product pages, and send your list for a quotation.

FactoryDan Phuong Industrial Cluster Phase 2, Dan Phuong Commune, Hanoi City, Vietnam
Slide 15 / 15