EI fire damper workshop
Details
Question answered: How are Starduct EI fire dampers made, and in what volume?
Symmetrical single-blade damper, 61.5 mm casing and blade, closed by torsion spring when the 70–74 °C fusible link releases; combinable for large ducts
| Model code | S-FSD-L210-0175.24 |
|---|---|
| Type | FD · fusible link |
| Fire class | EI 120 (measured EI 123) |
| Production sizes | W 200–2364 × H 200–1764 mm |
| Release | 70–74 °C |
| Casing length | L = 210 mm |
| Flange | (W + 164) × (H + 164) mm · TDC |
| Order code | S-FSD-L210-0175.24-2000x1500-TDC-EI120 |
| Test report | 0175-2024/TNCL |
|---|---|
| Laboratory | VLAT-2.0552 – Centre for Applied Research of Fire Science & Technology, University of Fire Prevention and Fighting |
| Date | 2024-03-27 |
| Standard | ISO 21925-1:2018 + TCVN 9311-1:2012 |
| Specimen | 1100 × 800 mm |
| Measured | EI 123 min · leakage during the fire test (test report §6.3) |
| Material test | MgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9 Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026 Test outside the laboratory’s VILAS accreditation scope |
Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.
Question answered: How are Starduct EI fire dampers made, and in what volume?
Question answered: Were tests really done, where, and for which models?
Document list being updated.
Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗
Messages are processed by AI to answer you; please do not enter sensitive information.