Back
EI 180 Measured (test report)
S-MFD-FS-L400

Insulated single-blade fire damper, Hoocon actuator

Insulated single-blade damper, 400 mm casing, Hoocon 5 Nm spring-return actuator; EI 180 to EN 1366-2 / ISO 21925-1

Quick select Production & QC Catalogue DoP BIM
Insulated single-blade fire damper, Hoocon actuator

Technical description

Model codeS-MFD-FS-L400
TypeMFD · actuator
Fire classEI 180 (measured EI 180)
Production sizesW 150–600 × H 150–600 mm
ReleaseHoocon HVD230S-5P 5 Nm
Casing lengthL = 400 mm
Flange(W + 64) × (H + 64) mm · TDC
Order codeS-MFD-FS-L400-400x300-TDC-EI180
Source: Measured (test report) · Fire resistance: EI 180 to EN 1366-2 / ISO 21925-1 (specimen 600 × 600 × 400 with Hoocon HVD230S-5P and enclosure, laboratory in Guangzhou, 2026; per Starduct leaflet, report shown to customers directly). Open pressure drop: Starduct internal measurement on FS samples 180 × 180 and 600 × 600 (AMCA 500-D-18 set-up, not third-party). Closed leakage: internal measurement on FSS-L210 samples 180 × 180 and 600 × 600 (same single-blade construction, cross-geometry).

Testing

Test reportSTARDUCT-INT-DP-2026-10
LaboratoryStarduct internal test room (Dan Phuong)
Date2026-10-12
StandardAMCA 500-D-18 (Fig. 5.3 / 5.1), assessed to AMCA 511
Specimen180 × 180 (Fig. 5.3), 600 × 600 (Fig. 5.1), same blade construction
Measuredopen-damper pressure drop 2.5–10 m/s
Test reportSTARDUCT-INT-LK-2026-10 · 2026-10-12 — closed leakage 300 / 500 / 1000 / 1500 Pa
Test reportEN 1366-2 / ISO 21925-1 fire test — report no. pending in Hub (shown to customers directly) · 2026-10-22 — EI 180 (180 min)
Material testMgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH
Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9
Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026
Test outside the laboratory’s VILAS accreditation scope

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

O&M manual · O&M training — EI fire dampers →

Production & QC

Process-stage videos

A0-6 Assembly 1 min 17 s

EI fire damper workshop

Details

Question answered: How are Starduct EI fire dampers made, and in what volume?

Evidence card
P8 Third-party testing 2 min 17 s

Two-sided fire test of an insulated fire damper to EN 1366-2

Details

Question answered: Were tests really done, where, and for which models?

Evidence card

Production & QC documents (ITP, procedures, sample records)

Document list being updated.

See the full factory audit

Quick select