EI 30 Measured (test report)
SAFD-L210

Insulated multi-blade make-up air fire damper, vertical blades

Vertical multi-blade damper installed in a wall opening between two fire compartments, supplying make-up air for smoke extraction; spring-return closing on power loss

Quick select Production & QC Catalogue DoP BIM
Insulated multi-blade make-up air fire damper, vertical blades

Technical description

Model codeSAFD-L210
TypeMFD · actuator
Fire classEI 30 (measured EI 33)
Production sizesW 150–800 × H 150–1200 mm
ReleaseFSLF24-S
Casing lengthL = 210 mm
Flange(W + 65) × (H + 65) mm · TDC
Order codeSAFD-L210-600x1000-TDC-EI30
Source: Measured (test report) · EI and leakage during the fire test: measured values from the test report. Free area ratio, ΔP, airflow and closed-damper leakage by size: calculated by the engine, outside the scope of the fire-resistance certification.

Testing

Test report0127-2024/TNCL-TT2
LaboratoryVLAT-2.0552 – Centre for Applied Research of Fire Science & Technology, University of Fire Prevention and Fighting
Date2024-10-24
StandardISO 21925-1:2018 + TCVN 9311-1:2012
Specimen800 × 1200 mm
MeasuredEI 33 min · leakage during the fire test (test report §6.3)
Material testMgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH
Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9
Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026
Test outside the laboratory’s VILAS accreditation scope

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

O&M manual · O&M training — EI fire dampers →

Production & QC

Process-stage videos

A0-6 Assembly 1 min 17 s

EI fire damper workshop

Details

Question answered: How are Starduct EI fire dampers made, and in what volume?

Evidence card
P8 Third-party testing 2 min 17 s

Two-sided fire test of an insulated fire damper to EN 1366-2

Details

Question answered: Were tests really done, where, and for which models?

Evidence card

Production & QC documents (ITP, procedures, sample records)

Document list being updated.

See the full factory audit

Quick select

Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗