EI 120 Measured (test report)
S-MFSD-L210-C

Extended combination fire damper with Belimo actuators

Assembly of single-blade S-MFSD-L210 modules (each ≤ 1200 × 800) with 174 mm mullions, mounted on the wall between two fire compartments; each module closes by spring return on power loss or fire alarm

Quick select Production & QC Catalogue DoP BIM
Extended combination fire damper with Belimo actuators

Technical description

Model codeS-MFSD-L210-C
TypeMFD · actuator
Fire classEI 120 (measured EI 136)
Production sizesW 500–2500 × H 500–1700 mm
ReleaseFSLF24-S
Casing lengthL = 210 mm
Flange(W + 164) × (H + 164) mm · TDC
Order codeS-MFSD-L210-C-2000x1600-TDC-EI120
Source: Measured (test report) · EI and leakage during the fire test: measured values from the test report. Free area ratio, ΔP, airflow and closed-damper leakage by size: calculated by the engine, outside the scope of the fire-resistance certification.

Testing

Test report0280-2024/TNCL
LaboratoryVLAT-2.0552 – Centre for Applied Research of Fire Science & Technology, University of Fire Prevention and Fighting
Date2024-05-21
StandardISO 21925-1:2018 + TCVN 9311-1:2012
Specimen2374 × 1774 mm
MeasuredEI 136 min · leakage during the fire test (test report §6.3)
Material testMgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH
Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9
Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026
Test outside the laboratory’s VILAS accreditation scope

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

O&M manual · O&M training — EI fire dampers →

Production & QC

Process-stage videos

A0-6 Assembly 1 min 17 s

EI fire damper workshop

Details

Question answered: How are Starduct EI fire dampers made, and in what volume?

Evidence card
P8 Third-party testing 2 min 17 s

Two-sided fire test of an insulated fire damper to EN 1366-2

Details

Question answered: Were tests really done, where, and for which models?

Evidence card

Production & QC documents (ITP, procedures, sample records)

Document list being updated.

See the full factory audit

Quick select

Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗