Back
EI 120 Measured (test report)
S-MFSD-L600-D

Insulated fire damper L600, two blades, one Belimo actuator

Two modules side by side in one casing, 100 mm mullion, two 58 mm blades driven by one actuator. For openings up to 2000 × 1000 mm.

Quick select Production & QC Catalogue DoP BIM
Insulated fire damper L600, two blades, one Belimo actuator

Technical description

Model codeS-MFSD-L600-D
TypeMFD · actuator
Fire classEI 120 (measured EI 120)
Production sizesW 1250–2000 × H 150–1000 mm
ReleaseFSNF24-S
Casing lengthL = 600 mm
Flange(W + 100) × (H + 100) mm · V40
Order codeS-MFSD-L600-D-1800x900-V40-EI120
Source: Measured (test report) · EI and leakage during the fire test: measured values from the test report. Free area ratio, ΔP, airflow and closed-damper leakage by size: calculated by the engine, outside the scope of the fire-resistance certification.

Testing

Test report332.22.KC.NCPCC
LaboratoryFire Safety Laboratory FSE (LAS-XD 416) – Vietnam Institute for Building Science and Technology (IBST)
Date2022-10-07
StandardISO 10294-1:1996 + TCVN 9311-1:2012
Specimen2000 × 1000 mm
MeasuredEI 120 min · leakage during the fire test (test report §6.3)
Material testMgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH
Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9
Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026
Test outside the laboratory’s VILAS accreditation scope

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

O&M manual · O&M training — EI fire dampers →

Production & QC

Process-stage videos

A0-6 Assembly 1 min 17 s

EI fire damper workshop

Details

Question answered: How are Starduct EI fire dampers made, and in what volume?

Evidence card
P8 Third-party testing 2 min 17 s

Two-sided fire test of an insulated fire damper to EN 1366-2

Details

Question answered: Were tests really done, where, and for which models?

Evidence card

Production & QC documents (ITP, procedures, sample records)

Document list being updated.

See the full factory audit

Quick select