EI fire damper workshop
Details
Question answered: How are Starduct EI fire dampers made, and in what volume?
Two modules side by side in one casing, 100 mm mullion, two 58 mm blades driven by one actuator. For openings up to 2000 × 1000 mm.
| Model code | S-MFSD-L600-D |
|---|---|
| Type | MFD · actuator |
| Fire class | EI 120 (measured EI 120) |
| Production sizes | W 1250–2000 × H 150–1000 mm |
| Release | FSNF24-S |
| Casing length | L = 600 mm |
| Flange | (W + 100) × (H + 100) mm · V40 |
| Order code | S-MFSD-L600-D-1800x900-V40-EI120 |
| Test report | 332.22.KC.NCPCC |
|---|---|
| Laboratory | Fire Safety Laboratory FSE (LAS-XD 416) – Vietnam Institute for Building Science and Technology (IBST) |
| Date | 2022-10-07 |
| Standard | ISO 10294-1:1996 + TCVN 9311-1:2012 |
| Specimen | 2000 × 1000 mm |
| Measured | EI 120 min · leakage during the fire test (test report §6.3) |
| Material test | MgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9 Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026 Test outside the laboratory’s VILAS accreditation scope |
Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.
Question answered: How are Starduct EI fire dampers made, and in what volume?
Question answered: Were tests really done, where, and for which models?
Document list being updated.
Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗
Messages are processed by AI to answer you; please do not enter sensitive information.