Back
EI 60 Measured (test report)
S-MFSD-WF

Insulated fire damper with KLB actuator

Two symmetrical blades in two sections (W > 1200 mm), installed in the wall between fire compartments, closing by spring return on power loss

Quick select Production & QC Catalogue DoP BIM
Insulated fire damper with KLB actuator

Technical description

Model codeS-MFSD-WF
TypeMFD · actuator
Fire classEI 60 (measured EI 62)
Production sizesW 150–1500 × H 150–600 mm
ReleaseCF-10NF230V-OS
Casing lengthL = 210 mm
Flange(W + 60) × (H + 60) mm · TDC
Order codeS-MFSD-WF-1000x500-TDC-EI60
Source: Measured (test report) · EI and leakage during the fire test: measured values from the test report. Free area ratio, ΔP, airflow and closed-damper leakage by size: calculated by the engine, outside the scope of the fire-resistance certification.

Testing

Test report0723-2025/TNCL-TT1
LaboratoryVLAT-2.0552 – Centre for Applied Research of Fire Science & Technology, University of Fire Prevention and Fighting
Date2025-10-13
StandardISO 21925-1:2018 + TCVN 9311-1:2024
Specimen1500 × 600 mm
MeasuredEI 62 min · leakage during the fire test (test report §6.3)
Material testMgSO₄ board 10 mm (casing and blades): Mould resistance, ASTM D3273-21 — 28 days, 32.5 °C, 95 % RH
Exposed (smooth) face rating 10; inner (mesh) face, pressed against the steel, rating 9
Vietnam Institute for Building Materials (VIBM) – VILAS 003 · 5391/VLXD-TTMT&CKXD · 22/10/2026
Test outside the laboratory’s VILAS accreditation scope

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

O&M manual · O&M training — EI fire dampers →

Production & QC

Process-stage videos

A0-6 Assembly 1 min 17 s

EI fire damper workshop

Details

Question answered: How are Starduct EI fire dampers made, and in what volume?

Evidence card
P8 Third-party testing 2 min 17 s

Two-sided fire test of an insulated fire damper to EN 1366-2

Details

Question answered: Were tests really done, where, and for which models?

Evidence card

Production & QC documents (ITP, procedures, sample records)

Document list being updated.

See the full factory audit

Quick select

Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗