Cable trays Derived from catalogue – not tested
SL
Cable ladder SL
Cable ladder for large power-cable routes needing maximum ventilation.
Technical description
| Model code | SL |
|---|---|
| Category | Cable trays |
| Production sizes | W 100–1200 × H 50/100/120/150/200 mm |
| Order code | SL-600x100-GI |
Source: Derived from catalogue – not tested
Testing
| Test report | 3469/VLXD-TBMT |
|---|---|
| Laboratory | VIBM – Vietnam Institute for Building Materials (Ministry of Construction), Centre for Equipment, Environment & Occupational Safety (CEELS) |
| Date | 2023-08-21 |
| Standard | TCVN 10688:2015 (IEC 61537:2006) |
| Specimen | Cable ladder system, Al+Zn+Mg coated steel (ZAM) and accessories 600W×100H×2.0T; SWL 4001 N/m; specimen submitted by QUACERT (certification test) |
| Measured | SWL 400 kg/m @ L 1 m (600×100 t 2 ZAM): deflection 2.35 / 2.43 mm (−5 / +60 °C); no damage at 680 kg · Impact 20 J at -5 °C: pass · Surface resistance: conductive (< 100 MΩ) · Electrical continuity of tray body: 0 mΩ/m (≤ 5 mΩ/m) · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0.1 % < A ≤ 0.25 % (rating 8 – ISO 10289) · Coating thickness 27.4 µm |
| Test report | 13732/VLXD-TBMT · 2019-12-16 — SWL 400 kg/m @ L 1 m (1200×200 t 2.5 S): deflection 5.52 / 5.88 mm (−5 / +60 °C); no damage at 680 kg · Impact 10 J at -5 °C: pass · Surface resistance: conductive (< 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0 % < A ≤ 0.1 % (rating 9 – ISO 10289) |
| Test report | 13734/VLXD-TBMT · 2019-12-16 — SWL 400 kg/m @ L 1 m (1200×200 t 2.5 P): deflection 5.48 / 5.64 mm (−5 / +60 °C); no damage at 680 kg · Impact 10 J at -5 °C: pass · Surface resistance: non-conductive (≥ 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0 % < A ≤ 0.1 % (rating 9 – ISO 10289) |
| Test report | 13733/VLXD-TBMT · 2019-12-16 — SWL 400 kg/m @ L 1 m (1200×200 t 2.5 P): deflection 5.48 / 5.64 mm (−5 / +60 °C); no damage at 680 kg · Impact 10 J at -5 °C: pass · Surface resistance: non-conductive (≥ 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0 % < A ≤ 0.1 % (rating 9 – ISO 10289) |
Documents
BIM / CAD downloads
Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.
Images & installation
Quick select
Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗