Cable trays Derived from catalogue – not tested
ST

Solid-base cable tray / trunking ST

Solid-base tray for protected cable routes; with an SCC cover it forms trunking.

Quick select Catalogue DoP BIM
Solid-base cable tray / trunking ST

Technical description

Model codeST
CategoryCable trays
Production sizesW 100–600 × H 50/75/100 mm
Order codeST-300x100-GI
Source: Derived from catalogue – not tested

Testing

Test report13735/VLXD-TBMT
LaboratoryVIBM – Vietnam Institute for Building Materials (Ministry of Construction), Centre for Equipment, Environment & Occupational Safety (CEELS)
Date2019-12-16
StandardTCVN 10688:2015 (IEC 61537:2006)
SpecimenNon-perforated cable tray, galvanised steel 2000×600×200, thickness 2.5; SWL 2056 N/m; specimen M4/17.46324
MeasuredSWL 205.3 kg/m @ L 1.5 m (600×200 t 2.5 GI): deflection 2.23 / 2.29 mm (−5 / +60 °C); no damage at 524 kg · Impact 5 J at -5 °C: pass · Surface resistance: conductive (< 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 1 % < A ≤ 2.5 % (rating 5 – ISO 10289)
Test report13736/VLXD-TBMT · 2019-12-16 — SWL 205.3 kg/m @ L 1.5 m (600×200 t 2.5 S): deflection 1.89 / 2.04 mm (−5 / +60 °C); no damage at 524 kg · Impact 5 J at -5 °C: pass · Surface resistance: conductive (< 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0 % < A ≤ 0.1 % (rating 9 – ISO 10289)
Test report2364/VLXD-TBMT · 2020-03-30 — SWL 34 kg/m @ L 1.5 m (200×100 t 0.95 GI): deflection 1.41 / 3.33 mm (−5 / +60 °C); no damage at 87 kg
Test report2365/VLXD-TBMT · 2020-03-30 — SWL 17 kg/m @ L 1.5 m (200×50 t 0.75 GI): deflection 2.23 / 2.11 mm (−5 / +60 °C); no damage at 35.7 kg
Test report2366/VLXD-TBMT · 2020-03-30 — SWL 102 kg/m @ L 1.5 m (600×100 t 1.5 GI): deflection 3.01 / 3.19 mm (−5 / +60 °C); no damage at 260 kg
Test report13737/VLXD-TBMT · 2019-12-16 — SWL 205.3 kg/m @ L 1.5 m (600×200 t 2.5 P): deflection 2.12 / 2.53 mm (−5 / +60 °C); no damage at 524 kg · Impact 5 J at -5 °C: pass · Surface resistance: non-conductive (≥ 100 MΩ) · Glow-wire 650 °C/30 s (TCVN 9900-2-11 / IEC 60695-2-11): no ignition; flame 1 kW/60 s (TCVN 9900-11-2 / IEC 60695-11-2): no flame spread · Neutral salt spray 96 h, NaCl 5 %, 35 °C (ISO 9227:2017): 0 % < A ≤ 0.1 % (rating 9 – ISO 10289)
Test report2363/VLXD-TBMT · 2020-03-30 — SWL 68 kg/m @ L 1.5 m (400×100 t 1.15 GI): deflection 3.04 / 3.17 mm (−5 / +60 °C); no damage at 173 kg

Documents

BIM / CAD downloads

Current family release (legacy code) — new-code version being updated. Direct download, no sign-in. To carry the performance of the selected size into your model, use the Quick selector.

Browse the full BIM library →

Quick select

Line quick selector with this model pre-selected. Project list, Submittal and DoP are printed from here. Open full screen ↗