0
Your cart0 Products
There are no products yet
Đại diện ngành sản xuất phụ kiện hệ thống MEP tại Việt Nam

NEWS

Part 4 – Notes on Installation, Operation, and Maintenance of VAV Systems
27/06/2025
Share
Đã copy link
“VAV systems are highly efficient and energy-saving—provided we remember to inspect them regularly.”

Installation & Commissioning Procedure

Proper installation is crucial to ensure the VAV system performs as designed. Key steps include:

  • Mechanical Installation

  • Mount and secure VAV boxes to the ceiling, ensuring airflow direction matches the sensor orientation (usually marked with an arrow).
  • Connect inlet and outlet ducts, insulate if needed, and install flexible connectors to reduce vibration and noise.
  • Install room temperature sensors in representative locations (avoid doors, windows, or vents).
  • Connect pressure sensor tubing (if using remote-mounted sensors) and ensure no leaks.
  • For reheat boxes, connect hot water pipes or electric heating wires correctly.
  • Ensure all valves and dampers operate smoothly.
  • ⚡ Electrical & Control Wiring

  • Connect 24 VAC or 220 VAC power to actuators and controllers.
  • Wire temperature and airflow sensors to the controller.
  • Set up communication networks (RS485 or TCP/IP) between VAV controllers and the central control panel.
  • Assign unique addresses/IDs to each VAV box to avoid conflicts.
  • Perform insulation and continuity checks for electrical safety.
  • 💻 Controller Programming & Configuration

  • Load the VAV control application into DDC controllers.
  • Configure parameters: network address, sensor-zone mapping, min/max airflow limits.
  • Calibrate I/O settings using DDC software and commission each VAV box:
    • Check damper travel range.
    • Verify temperature sensor accuracy.
    • Zero differential pressure sensors if needed (especially if installed at different altitudes).
  • 🌬️ Air Balancing

  • Measure actual airflow at diffusers using a balometer at max, min, and intermediate damper positions.
  • Calibrate airflow sensors to match measured values.
  • Ensure each VAV box delivers airflow within ±5% of design values.
  • Adjust AHU fan pressure: open all VAVs, measure pressure at the farthest point, and tune VFD speed accordingly.
  • Test automatic pressure control by closing some VAVs and observing system response.
  • 🧪 Testing & Commissioning

  • Run the system under peak and low-load conditions to verify control stability.
  • Simulate room heating to check VAV response and airflow increase.
  • Test interlocks:
    • If AHU fan stops, VAV dampers should fail open.
    • If fire alarm triggers, VAVs should open 100% for smoke extraction.
  • Test reheat function: simulate winter, verify hot water valve opens when airflow is at minimum but room is still cold.
  • Record final calibration values and generate a commissioning report.
  • ⚠️ Important: Clean ductwork before operation to prevent dust from jamming dampers. Ensure all AHU filters are installed to protect fans and sensors.

  • 🧰 Common Issues and Troubleshooting

  • 🔧 Sensor Failures

  • Faulty or drifted temperature sensors can cause overcooling or overheating.
  • Dirty or miscalibrated airflow sensors may misreport flow, leading to incorrect damper positions.
  • Solution: recalibrate sensors regularly (every 6–12 months).
  • ⚙️ Stuck Dampers or Actuator Failures

  • Dust or mechanical wear may cause dampers to stick or actuators to fail.
  • Symptoms: room temperature doesn’t change despite control signals.
  • Some actuators fail-safe to 100% open, causing overcooling.
  • Solution: inspect and replace actuators as needed.
  • 💨 Airflow Imbalance

  • “Starved box” issue: distant VAVs receive insufficient pressure, even at full open.
  • Nearby boxes may receive excess pressure, causing noise.
  • Solution: rebalance system, adjust duct dampers, or increase fan setpoint if capacity allows.
  • 🖥️ Control/BMS Errors

  • Communication loss or software bugs can disrupt operation.
  • Example: VAV reverts to standalone mode, losing optimization features.
  • Solution: check BMS logs and control logic.
  • 💧 Condensation or High Humidity

  • Too low supply air temperature or too little airflow can cause condensation at diffusers.
  • Solution: set minimum supply air temperature (~13°C) and airflow limits.
  • 🔊 Noise Issues

  • High inlet pressure causes whistling when dampers close too much.
  • Solution: reduce system pressure or install silencers.
  • Fan-powered VAVs may produce noise if bearings wear out.
  • 🧠 Expert Insight: After a decade, rubber and plastic parts degrade, sensors drift, actuators stick, and heating valves may leak—leading to poor temperature control and wasted energy.

  • 🛡️ Periodic Maintenance

  • 🌀 AHU & Chiller

  • Replace AHU filters every 3–6 months.
  • Clean cooling coils, check chilled water pumps, and inspect for condensation.
  • Maintain chillers annually (check refrigerant, oil, clean condenser).
  • 📦 VAV Box

  • Check room temperature sensors with a reference thermometer.
  • Verify airflow sensor accuracy using pressure taps.
  • Clean inside the box, especially dampers and sensors.
  • For fan-powered VAVs: lubricate or replace bearings if noisy.
  • Test actuators manually for smooth operation.
  • Inspect reheat valves: bleed air, check for leaks or stuck valves.
  • 🧠 Control System

  • Check controller backup batteries.
  • Regularly back up BMS programs and databases.
  • Update firmware as recommended.
  • 📊 Tip: Use BMS trending to detect anomalies—e.g., rooms with large temperature swings or excessive reheat usage.

  • 🧼 Duct & Diffuser Cleaning

  • Clean every 3–5 years to maintain air quality and sensor accuracy.
  • 👨‍🏫 Operator Training

  • Train staff to recognize BMS alarms, understand system diagrams, and manually operate valves during failures.
  • Keep maintenance logs and manuals up to date.

Bình luận (0)

/images/logo.png
Related Articles
27/06/2025
Part 4 – Notes on Installation, Operation, and Maintenance of VAV Systems
27/06/2025
Part 1-Comparison of VAV and VRF Systems
27/06/2025
PART 3- VAV SYSTEM Control and Monitoring Strategies
20/07/2025
PART 7: CALCULATING AIRFLOW, PRESSURE AND SELECTING VAV BOXES
22/07/2025
Part 10: Multi-Zone Variable Air Volume (VAV) System?
27/06/2025
PART 2 - Efficient VAV System Design
04/07/2025
How Does a VAV Box Work?
07/07/2025
VAV SYSTEM DESIGN STANDARDS
Success
Add to cart successfully
Success
Logged in successfully
Fail
null
Fail
Please login to view details!
Success
Bình luận đã được gửi thành công và đang chờ duyệt!
Fail
Có lỗi xảy ra khi gửi bình luận. Vui lòng thử lại!